Doo doo doo, lookin’ out my back (fire) door…

Something old and something new(ish): old rant, new requirement.

As we move ever onwards toward the close of our first year “under” the 2012 Life Safety Code® (talk about a brave new world), there was one item of deadline that I wanted to touch upon before it got too, too much further into the year. And that, my friends, is the requirement for an annual inspection of fire and smoke door assemblies—for those of you keeping track, this activity falls under the EOC chapter under the standard with all those other pesky life safety-related inspection, testing, and maintenance activities (don’t forget to make sure that your WRITTEN documentation of the door assembly inspection includes the appropriate NFPA standards reference—in this case, you have quite a few to track: NFPA 101-2012 for the general requirements; NFPA 80-2010 for the fire door assemblies; and, NFPA 105-2010 for the smoke door assemblies). Also, please, please, please make sure that the individual(s) conducting these activities can “demonstrate knowledge and understanding of the operating components of the door being tested” (if this sounds like it might be a competency that might need to be included in a position description and performance evaluation, I think you just might be barking up the correct tree). The testing is supposed to begin with a pre-test visual inspection, with the testing to include both sides of the opening. Also, if you are thinking that this is yet another task that will be well-served by having an inventory, by location, of the door assemblies, you would indeed be correct (to the best of my knowledge). As a caveat for this one, please also keep in mind that this would include shaft access doors, linen and trash chute—while not exactly endless, the list can be pretty extensive. At the moment, from all I can gather, fire-rated access panels are optional for inclusion, though I don’t know that I wouldn’t be inclined to have a risk assessment in one’s back pocket outlining the decision to include or not to include (that is the question!?!) the access panels in the program.

I’m thinking you will probably want to capture this as a recurring activity in your work order system, as well as developing a documentation form. Make sure the following items are covered in the inspection/testing activity:

 

  • No open holes or breaks in the surfaces of either the door or the frame
  • Door clearances are in compliance (no more than ¾ inch for fire doors; no more than 1 inch for corridor doors; no more than ¾ inch for smoke barrier doors in new buildings)
  • No unapproved protective plates greater than 16 inches from the bottom of the door
  • Making sure the latching hardware works properly
  • If the door has a coordinator, making sure that the inactive door leaf closes before the active leaf
  • Making sure meeting edge protection, gasketing, and edge seals (if they are required—depends on the door) are inspected to make sure they are in place and intact

 

I think the other piece of the equation here is that you need to keep in mind that “annual” is a minimum frequency for this activity; ultimately, the purpose of this whole exercise is to develop performance data that will allow you to determine the inspection frequency that makes the most sense for compliance and overall life safety. Some doors (and I suspect that you could rattle off a pretty good list of them without even thinking about it too much) are going to need a little more attention because they “catch” more than their fair share of abuse (crash, bang boom!). Now that this isn’t an optional activity (ah, those days of the BMP…), you might as well make the most of it.

 

Putting on my rant-cap, I’d like to steal just a few moments to lament the continuing decline of decency (it used to be common; now, not so much) when it comes to interactions with strangers (and who knows, maybe it’s extending into familial and friendial interactions as well—I sure hope not!) I firmly believe that any and every kindness should be acknowledged, even if it’s something that they were supposed to do! My favorite example is stopping for pedestrians (and if you’ve been behind me, yes that was me stopping to let someone complete the walk); yes, I know that in many, if not most, places, the law requires you to stop for pedestrians in a crosswalk, but I think the law should also require acknowledgement from the pedestrians. Positive reinforcement can’t possibly hurt in these types of encounters. Allowing merging traffic to move forward (signaling is a desirable approach to this, but you should also signal the person who let you in). I’m not sure if we’re just out of practice or what, but I’d ask you to just try a little more to say “hi” or “thanks” or give somebody a wave when they aren’t jerks (and just so we’re straight, a wave includes more than just the middle digit). Maybe I’m going a little Pollyanna here, but the world is just not nice enough lately. Hopefully we can make an incremental improvement…

Entry Information

Filed Under: Environment of careHospital safetyLife Safety Code

Tags:

Steve MacArthur About the Author: Steve MacArthur is a safety consultant based in Bridgewater, Mass. He brings more than 30 years of healthcare management and consulting experience to his work with hospitals, physician offices, and ambulatory care facilities across the country. He is the author of HCPro's Hospital Safety Director's Handbook and is contributing editor for Briefings on Hospital Safety. Contact Steve at stevemacsafetyspace@gmail.com.